C
carlos39Aug 19, 2025
Why won't the compressor start in my FRIULAIR CWE 068 Chiller?
- JJames LewisAug 19, 2025
If the compressor in your FRIULAIR Chiller isn't starting, here are a few things to check: * If the thermal protection inside the compressor activated, wait for it to cool down and ensure the compressor is working under normal conditions. Also, check for insufficient refrigerant. * Examine the compressor contactor. Verify the voltage at the coil and the coil's continuity. * If the phase-sequence relay intervened, reverse the two phases upstream from the unit's electrical panel cut-off switch. * If the magnetothermic protection of the compressors opened, look for short circuits in the motor windings. Check for over-absorption of current due to low voltage, and verify the power supply voltage and operating conditions.