The UPS offers four relay (Input abnormal, Low battery, UPS alarm, On-Bypass).
The signal can output the open or the close. Moreover, it provides with the
terminal of REPO (REMOTE ON/OFF) and a Remote Shutdown.
Table 9-2 Terminal on PCB(M4)
No Terminal Signal I/O Jumper Relay Note
1-2 OPEN
1 P1-P2
Input
abnormal
Out JP1
3-2 CLOSE
1-2 OPEN
2 P3-P4
Low
battery
Out JP2
3-2 CLOSE
1-2 OPEN
3 P5-P6 UPS alarm Out JP3
3-2 CLOSE
1-2 OPEN
JP4
3-2 CLOSE
DC30V MAX 2A MAX
AC125V MAX 0.5A MAX
1-2 - On-Bypass output possible
4 P7-P8 On-Bypass Out
JP5
3-2 - On-Bypass output impossible
・Choose the ring tongue terminal of the size that suits M4
・Cover and mount the sleeve on the ring tongue terminal.
Table 9-3 Terminal
No Terminal Signal I/O Spec Note
5 REPO
REPO
REMOTE ON/OFF
In 10mA MAX
This is used for an urgent stop or
remote ON/OFF.
6 RSD
Remote shut
down
In 5V~30V
When remotely shutting down, This is
used.
Prepare the line kind of the following condition in the connection to this terminal.
Table 9-4 Condition
Item Content
Kind Twist or Shield
DIA AWG22~16
Torque 5 lbf・in
Screw M3
Stripping Length 6~7mm
・Defend and use the connection condition and the signal specification. There is a
possibility of damaging it besides.
・Do the static electricity measures when you connect it.