EasyManua.ls Logo

Fuji Electric PEN152J1RT/15 - Chapter 9 Optional card; Network Agent Card

Fuji Electric PEN152J1RT/15
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
1 2 345 6 7 8
LED
1
LED
2
LED1
LED2
Chapter9
Optional card
The following card is prepared in the UPS with optional.
・Network Agent card(Option)
:Cooperation with Power Management Software (Power-SOL). It is
a card equipped with SNMP agent's function.
Dry Contact cardOption
It is a card equipped with 4 Relay Outputs(Input abnormal, Low
battery, UPS alarm, On-Bypass). It provides with REPO (REMOTE
ON/OFF) function and the remote shutdown function
9-1 Network Agent Card
Externals are shown in Figure 9-1.
Figure 9-1 Network Agent Card
(1)Network port
The card communicates with the administrative terminal where power
supply management software Power-SOL was installed by way of the
network by using this communication port.
The transmission rate corresponds
to 10Mbps/100Mbps.
The hot-swap of the card is possible.
Figure -2 Network port
The pin layout and externals of the port and position of LED that shows
communication are shown in Figure 9-2
.
LED1: The state of 10BASE-T /100BASE-TX is shown.
LED2: The communication with UPS is shown.