2-20. E: 65. IPM error (Outdoor unit)
Detective actuator Outdoor unit
Main PCB 1. →hen more than normal operating current to IPM in
main PCB flows, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Compressor
Forecast of cause
Defective connection of electric components
Outdoor fan operation failure
Outdoor heat exchanger clogged
Compressor failure
Main PCB failure
Check point 1. Check connections of outdoor unit electrical components
Check if the terminal connection is loose.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
 Upon correcting the removed connector or mis-wiring, reset the power.
Check point 2. Check outdoor fan and heat exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of outdoor heat exchanger?
Is the fan rotating by hand when operation is off?
 If the fan motor is locked, replace it.
Check point 3. Check outdoor fan
Check outdoor fan motor. (Refer to "E: 97. Outdoor unit fan motor error (Outdoor unit)" on page 03-
32.)
 If the fan motor is failure, replace it.
2-20. E: 65. IPM error (Outdoor unit) - (03-24) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ACUH09LUAS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ACUH09LUAS1 and is the answer not in the manual?

Fujitsu ACUH09LUAS1 Specifications

General IconGeneral
BrandFujitsu
ModelACUH09LUAS1
CategoryAir Conditioner
LanguageEnglish

Related product manuals