NOTES:
Strainer normally does not have temperature difference between inlet and outlet as shown be-
low.
Pipe (In) Pipe (Out)
If there is a difference like shown below, there is a possibility of inside clogged. In this case, re-
place the strainer.
Pipe (In) Pipe (Out)
3-4. No cooling/No heating - (03-41) - 3. Troubleshooting without error code