En-6
Fork (Forklift)
Delivery pallet
Fork (Forklift) or
Fork (Manual forklift)
<Front>
<Side>
3. 5. Installation the unit
• Install the unit level. (within 3 degrees).
• Install 4 or more anchor bolts at the 8 locations indicated by arrows (Fig. A).
• Place the left and right anchor bolts at a distance further away than the dimensions
of A in the Table A.
(Excluding the case where anchor bolts are installed at 8 places.)
Fig. A
Hole: 12 × 17
(8 places)
Bottom view
(Unit: mm)
732
765
80
80
160160
B
A
Table.A
Model A B
AJ
072LALBH 610 930
AJ
090LALBH 610 930
AJ
108LALBH 920 1240
AJ
126LALBH 920 1240
AJ
144LALBH 920 1240
AJ
162LALBH 920 1240
• To minimize vibration, do not install the outdoor unit directly on the ground.
Instead, install it on top of a fi rm platform (such as concrete block). (Fig. B)
• The foundation base should be able to support the product and the foot width of
the product should be more than 46.5mm.
• Depending on the installation condition, vibration during the operation of the unit
may cause noise and vibration.
Install vibration-proofi ng materials (such as rubber pads).
• Consider the removal space of the connection piping when installing the founda-
tion.
• Secure the equipment fi rmly with anchor bolts, washers, and nuts.
Fig. B
Bolt (M10)
*Do not use a four-corner support foundation.
GOODPROHIBITED GOOD
Fig. C
200mm or
more
When installing pip-
ing from the bottom
of the outdoor units,
the required space
under the outdoor
unit ≥ 200mm.
* Install the branch
kit horizontally.
4. SYSTEM CONFIGURATION
4. 1. System confi guration
CAUTION
• When connecting multiple outdoor units, set the nearest outdoor unit to the indoor
unit on the refrigerant pipe as the master unit.
• When connecting multiple outdoor units, install the outdoor unit with the largest
nominal system capacity nearest to the indoor unit on the refrigerant pipe, fol-
lowed by those with less nominal system capacities.
[Capacity: Master ≥ Slave]
• Always keep to the limit on the total amount of refrigerant. Exceeding the limit
on the total amount of refrigerant when charging will lead to malfunction.
A) In case of 1 outdoor unit connected
Fig. A
O.U.
(Master)
O.U. :Outdoor unit
I.U. :Indoor unit
I.U.
I.U. I.U. I.U.
I.U.
I.U. I.U. I.U. I.U.
f
p
H2
H1
H3
a
g
q
• Allowable pipe length (actual pipe length)
Between master outdoor unit and the
farthest indoor unit
165 m or less
a+f
a+p
Between the fi rst separation tube and the
farthest indoor unit
90 m or less f, p
(farthest indoor unit)-(closest indoor unit) 60 m or less f (p) - g (q)
Total pipe length 700 m or less Total
• Allowable height difference
Between outdoor unit and indoor unit (When
indoor unit is installed below)
50 m or less
H1
Between outdoor unit and indoor unit (When
outdoor unit is installed below)
40 m or less
Between indoor units 15 m or less H2, H3
• Total refrigerant amount : 31.5 kg or less
B) In case of 2 outdoor units connected
Fig. B
O.U.-2
(Slave)
O.U.-1
(Master)
f
e
a
g
q
H4
p
H1
H2
H3
b
O.U. :Outdoor unit
I.U. :Indoor unit
I.U.
I.U.
I.U.
I.U.
I.U.
I.U.
I.U.
I.U. I.U.
• Allowable pipe length (actual pipe length)
Between master outdoor unit and the
farthest indoor unit
165 m or less
a+e+f
a+e+p
Between the fi rst separation tube and the
farthest indoor unit
90 m or less f, p
(farthest indoor unit)-(closest indoor unit) 60 m or less f (p) - g (q)
Total pipe length 1000 m or less Total
Between outdoor unit and outdoor unit
branch kit
3 m or less a, b
9378945180-02_IM.indb 69378945180-02_IM.indb 6 2014/11/10 19:39:562014/11/10 19:39:56