3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢ Fan speed
Indoor fan speed is defined as below.
Operation mode Fan mode
Speed (rpm)
ASEH30KMTB
ASEH36KMTB
Heating
POWERFUL 1,520
HIGH 1,330
MED+ 1,260
MED 1,100
LOW 950
QUIET 780
Cool air prevention 600
S-LOW 540
Cooling/Fan
POWERFUL 1,520
HIGH 1,330
MED 1,100
LOW 950
QUIET 780
Soft quiet
600*
1
S-LOW
540*
2
Dry
X zone: 780
J zone: 680
*1: Fan mode only
*2: Cooling mode only
3-1. Indoor fan control - (04-8) - 3. Fan control