2-12. E: 63. Inverter error (Outdoor unit)
Indicator
Indoor unit
Operation indicator 6 time flash
Timer indicator 3 time flash
Economy indicator Continuous flash
Error code E: 63
Outdoor unit Refer to "Error code table (Outdoor unit)" on page 03-3
Detective actuator Outdoor unit Inverter PCB Error information received from inverter PCB
Forecast of cause
External cause
Power supply to inverter PCB wiring disconnection or
open
Inverter PCB failure
Check point 1. Turn the power on again?
If no, go to "Check point 1-2".
Error displayed again?
Check point 2. Check the wiring (power supply to inverter PCB)
Connector and wiring connection state check
Cable open check
Check point 3. Replace inverter PCB
Replace inverter PCB
End
Check point 1-2. Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
End