Available Sensor ID
Sensor ID Item Unit Remarks
00 158
Cooling thermostat On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 159
Requested cooling strength On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 160
External heater On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 161
Heating operation status (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 162
External output command by remote
controller (External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 163
Set-point temp. not reached in server
room function On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
01: Outdoor unit
01 000 Outdoor temp. 01: °C or °F
01 001 Discharge temp. 01: °C or °F
01 003 Heat exchanger middle temp. 01: °C or °F
01 004 Heat exchanger outlet temp. 01: °C or °F
01 007 Compressor temp. 01: °C or °F
01 042 Gas pipe pressure for outdoor unit 02: MPa
01 050 Fan 1 rotation number 03: rpm
01 055 Compressor rotation number 04: rps
01 060
Expansion valve (Upstream during
heating)
05: pls
01 080 4-way valve output status
07: Cooling/
Heating
0: Cooling, 1: Heating
01 085 Pressure switch (High pressure) 08: On/Off 0: Off (Close), 1: On (Open)
01 100 Operating current 09: A
01 110 Outdoor unit total power-on hours 11: h
01 111
Compressor total heating operation
hours
11: h
01 112
Compressor total cooling operation
hours
11: h
01 113 Compressor total operation hours 11: h
01 114
Outdoor unit fan 1 total operation
hours
11: h
01 145
Outdoor low noise input (External
input)
00: — 0: Off, 1: On
01 146 Outdoor peak cut (External input) 00: —
0: Off
1: Mode 4 (100%)
2: Mode 3 (75%)
3: Mode 2 (50%)
4: Mode 1 (Forced thermostat off)
01 147 Demand response (External input) 00: —
0: Normal, 1: DRM1, 2: DRM2, 3:
DRM3
7-16. Unit status monitoring and the detected value indication - (04-29) - 7. Various control