2-8. FUNCTION DETAILS
Function
Function
number
Setting number Default Details
Filter
indicator
interval
11
00
Default
Adjust the lter cleaning interval notication. If the notication is too
early, change to setting 01. If the notication is too late, change to
setting 02.
01
Longer
02
Shorter
Filter
indicator
action
13
00
Enable
Enable or disable the lter
indicator. Setting 02 is for use
with a central remote control.
01
Disable
02
Display only on
central remote
control
Ceiling
airow
20
00
Default
Regulate the airow according to the needs of the installation location.
When set to 01, the airow will be stronger. (Cassette type only)
01
High Ceiling
Vertical
airow
direction
23
00
Default
Adjust the vertical airow direction. All airow direction louvers are
adjusted together.
(Cassette type only)
01
Raise
Horizontal
swing
airow
direction
24
00
Default
Adjust the horizontal swing airow direction.
(For horizontal swing equipped models)
01
Left half
02
Right half
Static pressure
26
00
SP mode 00
Model name
Range of static
pressure mode
Normal static
pressure
ARUL4TLAV1 SP mode 00 to 03
0.04 in.WG
(10 Pa)
ARUL7TLAV
SP mode 00 to 09
0.10 in.WG
(25 Pa)
ARUL9TLAV
ARU L12 TL AV
ARU L14TL AV
ARUL18TLAV
ARUM24TLAV SP mode 00 to 14
0.16 in.WG
(40 Pa)
ARUM30TLAV SP mode 00 to 11
ARUM36TLAV SP mode 00 to 09
ARUH36TLAV SP mode 02 to 16
0.40 in.WG
(100 Pa)
ARUH72TLAV1 SP mode 05 to 30
0.60 in.WG
(150 Pa)
ARUH96TLAV SP mode 05 to 29
Refer to "7. FAN PERFORMANCE CURVE" in Chapter 4 for the
characteristics of each indoor unit.
01
SP mode 01
02
SP mode 02
03
SP mode 03
04
SP mode 04
05
SP mode 05
06
SP mode 06
07
SP mode 07
08
SP mode 08
09
SP mode 09
10
SP mode 10
11
SP mode 11
12
SP mode 12
13
SP mode 13
14
SP mode 14
15
SP mode 15
16
SP mode 16
17
SP mode 17
18
SP mode 18
19
SP mode 19
20
SP mode 20
21
SP mode 21
22
SP mode 22
23
SP mode 23
24
SP mode 24
25
SP mode 25
26
SP mode 26
27
SP mode 27
28
SP mode 28
29
SP mode 29
30
SP mode 30
31
Normal SP
Cool air tem-
perature trigger
30
00
Default
Adjust the cool air trigger temperature. To lower the trigger
temperature, use setting 01. To raise the trigger temperature,
use setting 02.
01
Adjust (1)
02
Adjust (2)
Heat air tem-
perature trigger
31
00
Default
Adjust the heat air trigger temperature. To lower the trigger
temperature by 6 degrees C, use setting 01. To lower the trigger
temperature by 4 degrees C, use setting 02. To raise the trigger
temperature, use setting 03.
01
Adjust (1)
02
Adjust (2)
03
Adjust (3)
- (07 - 112) -
FUNCTION
SETTING
FUNCTION
SETTING