9. OPTIONAL PARTS INSTALLATION
9-1. DRAIN PUMP UNIT
MODEL: UTZ-PU1NBA
z
Specications
Unit Specications
Pump Lift-up in. (mm) Maximum 39-3/8 (1
,
000)
Power source - 220-240V, 50/60Hz
Input Power (230V, 50/60Hz) W 12 / 10.8
Current (230V, 50/60Hz) mA 114 / 92
Dimensions (H × W × D) in. (mm) 6-15/16 × 7 × 6-1/16 (176 × 178 × 154)
Weight lbs. (kg) 6 (2.5)
Connection pipe diameter in. I.D.3/4, O.D.1-1/16
Direction of pipe connection
*
1 - 360°
Angle of pipe connection
*
2 - 0° (Horizontal)-90° (Vertical)
Control method - Control board of indoor unit
safety device - Float switch, Thermal fuse
z
Application indoor units
Type Model name
Duct ARUM24TLAV, ARUM30TLAV, ARUM36TLAV
z
Mounting position
*
1: Direction of pipe connection
*
2: Angle of pipe connection
Max. 39-3/8 (1000)
6-7/16 (163)
6-15/16 (176)
1-13/16 (46)
10-5/8 (270)
Connected drain pipe
I.D.3/4, O.D.1-1/16
Rear view
Unit: in. (mm)
Front view
19 (470) or more
6 (150) or more
31 (787)
6-1/16 (154)
4-9/16
(116)
6-9/16
(166)
46-5/16 (1177)
29-1/8 (740)
44-11/16 (1135)
18-3/4 ~ 21-5/8
(477 ~ 550)
7 (178)
Drain pump unit
Top view
Air
NOTE:
Leave space to service the unit. Make sure that a
service access is left near the drain pump.