Fujitsu AJYA36LALH - Checklist; 10 LED Display; Normal Operation Mode; Error Display Mode

Fujitsu AJYA36LALH
23 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-22
Checklist9. 4.
Check description Check method Criteria
1
High and low pressure values
are normal.
Check it with a pres-
sure gauge.
Cooling: low pressure
approx. 0.8 MPa
Heating: high pressure
approx.
3.0 MPa
2
Drain water is discharged
smoothly through the drain
hose.
Check it by pouring
water.
3
Indoor and outdoor unit fans
are operating.
Check them visually.
4
Compressor operates after
the indoor unit operates.
Check the operating
sound.
5
Difference between inlet and
outlet temperatures is normal.
Measure the inlet and
outlet temperatures.
Temperature difference
10 degrees
6 Error is not displayed
Check the 7 segment
display
Error blinking or no error
code display
LED Display10.
You can determine the operating status by the lighting up and blinking of the LED dis-
play.
Check the status using the table below.
Normal operation mode10. 1.
Mode CODE DESCRIPTION
Operation
CL Cooling
Ht Heating
o r During oil recovery operation
d F During defrosting operation
P C During power saving operation
L n During low noise operation
Error display mode10. 2.
Mode CODE DESCRIPTION
Communication
error
E 1 4. 2 Outdoor unit network communication 2 error
E 1 4. 5 The number of indoor unit shortage
Indoor unit
actuator error
E 5 U. 1 Indoor unit miscellaneous error
Outdoor unit
PCB/Electrical
component/
Switch error
E62.3Outdoor unit EEPROM access error
E 6 2. 6 Outdoor unit inverters communication error
E 6 2. 8 Outdoor unit EEPROM data corruption error
E 6 3. 1 Outdoor unit inverter error
E67.2
Outdoor unit inverter PCB power short interrup-
tion error
E68.2
Outdoor unit rush current limiting resister temp.
rise error (protective operation)
E69.1
Outdoor unit transmission PCB parallel com-
munication error
Outdoor unit
sensor error
E 7 1. 1 Outdoor unit discharge temp. thermistor 1 error
E72.1
Outdoor unit compressor temp. thermistor 1 error
E73.3
Outdoor unit heat ex. liquid temp. thermistor error
E 7 4. 1 Outside air temp. thermistor error
E 7 5. 1 Outdoor unit suction gas temp. thermistor error
E 7 7. 1 Outdoor unit heat sink temp. thermistor error
E82.1
Outdoor unit sub-cool heat ex. gas inlet temp.
thermistor error
E82.2
Outdoor unit sub-cool heat ex. gas outlet temp.
thermistor error
E 8 3. 2 Outdoor unit liquid pipe temp. thermistor 2 error
E84.1
Outdoor unit current sensor 1 error
(permanent stop)
E 8 6. 1 Outdoor unit discharge pressure sensor error
E 8 6. 3 Outdoor unit suction pressure sensor error
E 8 6. 4 Outdoor unit high pressure switch 1 error
Outdoor unit
actuator error
E 9 3. 1 Outdoor unit inverter compressor start up error
E 9 4. 1 Outdoor unit trip detection
E95.5
Outdoor unit compressor motor loss of synchro-
nization
E 9 7. 1 Outdoor unit fan motor 1 lock error
E 9 7. 4 Outdoor unit fan motor 1 undervoltage
E97.5
Outdoor unit fan motor 1 temperature error
(protective action)
E98.1Outdoor unit fan motor 2 lock error
E98.5
Outdoor unit fan motor 2 temperature error
(protective action)
E 9 A. 1 Outdoor unit coil 1 (expansion valve 1) error
E 9 A. 2 Outdoor unit coil 2 (expansion valve 2) error
Refrigerant
system error
EA1.1
Outdoor unit discharge temperature 1 error
(permanent stop)
EA3.1
Outdoor unit compressor 1 temperature error
E A 4. 1 Outdoor unit high pressure error
E A 4. 2 Outdoor unit high pressure protective action 1
E A 5. 1 Outdoor unit low pressure error
E A C. 4 Outdoor unit heat sink temperature error
㪜㪛㩷㫃㪸㫄㫇㩷㪑
㪃㪃 㪃㪃
㪣㪑
㪡㪑
㪍㪑
㪃㪃
㫅㪑
㫉㪑 㫋㪑
㪃㪃
㪬㪑
㪐㪑㪏㪑
㪃㪃
㪻㪑㪪㪑
㪘㪑
㪝㪑
㪚㪑 㪜㪑
㪇㪑
㪌㪑
㪃㪃
㪃㪃
㪊㪑㪈㪑 㪉㪑
㪎㪑
㪋㪑
INFORMATION11.
Main contents of label
Item Detail
Model name 1. Model name
Serial number 2. Serial number
Electric characteristics 3. Phase, rated voltage, and frequency
Weight 4. Product weight
Capacity 5.
Cooling/heating capacity under cooling/
heating condition (refer to item 15)
Current 6.
Electric current during cooling/heating
operation under cooling/heating condition
(refer to item 15)
Input power 7.
Input during cooling/heating operation
under cooling/heating condition (refer to
item 15)
Max. Current 8.
Maximum electric current (temperature
condition is max. cooling condition [refer
to item 16])
Air circulation 9. Air circulation
Noise level10. Noise level
Refrigerant11.
Refrigerant type and initial charging
amount
Max. pressure (HP/LP)12.
Means pressure of High Pressure side/
Low Pressure side
Protection13. Protection level against dust and water
Working temperature14. Working temperature
Condition of cooling/heating15.
Dry-bulb temperature and wet-bulb tem-
perature under standard cooling/heating
condition
Condition of max. cooling16.
Dry-bulb temperature and wet-bulb tem-
perature at maximum electric current and
input
Manufacture year17. Manufacture year
Origin18. Origin country
Manufacturer19.
Manufacturer
FUJITSU GENERAL LIMITED
Address: 1116, Suenaga, Takatsu-ku,
Kawasaki 213-8502, Japan
9380545026-02_IM.indb 229380545026-02_IM.indb 22 19/08/2013 17:20:1219/08/2013 17:20:12

Related product manuals