External heater output
Control Primary heater Auxiliary heater
Function setting
Indoor unit Wired R. C.
Control switching
external heaters
No. 61
Sensor activation*
2
Auxiliary heater
control 1
Heat pump
External device*
1
61-00
Auxiliary heater
control 2
Heat pump External device 61-01
Heat pump prohibition
control
External device None 61-02 On (Enabled)
Auxiliary heater
control by outdoor
temperature 1
Heat pump External device 61-03 On (Enabled)
Auxiliary heater
control by outdoor
temperature 2
Heat Pump External device 61-04 On (Enabled)
Auxiliary heater
control by outdoor
temperature 3
Heat Pump External device 61-05 On (Enabled)
Auxiliary heat pump
control
External device Heat pump 61-06 On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 1
External device Heat pump 61-07 On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 2
External device Heat pump 61-08 On (Enabled)
Auxiliary heat pump
control by outdoor
temperature 3
External device Heat pump 61-09 On (Enabled)
NOTES:
After turning off the heater, 3 minutes of standby time is required by next power-on of the
heater.
For items marked “—” in the table, any of validate or invalidate of the setting are acceptable.
*1: External device means Hot water, Electrical heater, etc.
*2: Sensor activation:
Setting change from the factory setting is required.
Indoor unit fan setting will be on for safety reason without sensor activation of wired remote
controller.
4-4. Details of function
- (05-34) - 4. External input and output
FIELD
WORKING
FIELD
WORKING