12. Safety devices
Type of
protection
Protection form
Model
AOYG30KBTA4
Circuit protection
Current fuse
(Main PCB)
250 V, 5 A
250 V, 20 A
250 V, 3.15 A
Fan motor
protection
Thermal protector
Activate
125 ±10°C
Fan motor stop
Reset
120 ±10°C
Fan motor restart
Compressor
protection
Temperature thermistor
(Discharge temp.)
Activate
110°C
Compressor stop
Reset
After 7 minutes
Compressor restart
Temperature thermistor
(Compressor bottom temp.)
Activate
108°C
Compressor stop
Reset
After 3 minutes, and 80°C or less
Compressor restart
Thermal protection program
(Outdoor temp.)
(Only in COOL or DRY mode)
Activate
-20°C
Compressor stop
Reset
-15°C
Compressor restart