Type
Cassette
Inverter heat pump
Model name AUXG45KRLB AUXG54KRLB
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 12.1 13.4
Btu/h 41,300 45,700
Min.—Max.
kW 4.00—12.60 4.50—13.80
Btu/h 13,600—43,000 15,400—47,100
Heating
Rated
kW 13.5 15.5
Btu/h 46,000 52,900
Min.—Max.
kW 4.20—15.00 4.70—16.00
Btu/h 14,300—51,200 16,000—54,600
Input power
Cooling
Rated
kW
4.32 4.87
Max. 5.00 5.23
Heating
Rated 3.77 4.86
Max. 4.69 4.77
Current
Cooling
Rated A
18.8 21.4
Heating 16.6 21.3
Power factor
Cooling
%
99.7 99.0
Heating 99.0
EER Cooling
kW/kW
2.80 2.75
COP Heating 3.58 3.19
Moisture removal L/h (pints/h) 4.5 (7.9) 5.0 (8.8)
Maximum operating current *1
Cooling
A
28.1
Heating 28.1
Fan
Airflow rate
Cooling
HIGH
m
3
/h
2,000 2,100
MED 1,650 1,780
LOW 1,460 1,600
QUIET 1,300 1,320
Heating
HIGH 2,000 2,100
MED 1,650 1,780
LOW 1,460 1,600
QUIET 1,300 1,320
Type × Q'ty Turbo fan × 1
Motor output W 81
Sound pressure level *2
Cooling
HIGH
dB (A)
46 47
MED 42 43
LOW 39 40
QUIET 35 36
Heating
HIGH 46 47
MED 42 43
LOW 39 40
QUIET 35 36
Heat exchanger type
Dimensions (H × W × D)
mm
Main1: 252 × 2,131 × 13.3
Main2: 252 × 2,064 × 13.3
Main3: 252 × 1,999 × 13.3
Fin pitch
Main1: 1.3
Main2: 1.3
Main3: 1.3
Rows × Stages
Main1: 1 × 12
Main2: 1 × 12
Main3: 1 × 12
Pipe type Copper tube
Fin type Aluminum
Dimensions
(H × W × D)
Net
mm
288 × 840 × 840
Gross 340 × 960 × 950
Weight
Net
kg
29
Gross 34
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Drain hose
Material PVC
Size mm Ø 25 (I.D.), Ø 32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Cassette grille
(Option)
Model name
UTG-UKYC-W
Material Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
mm
53 × 950 × 950
Gross 110 × 1,000 × 1,010
Weight
Net
kg
6.0
Gross 10.0
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
1-1. Indoor unit
- (01-4) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION