Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
Circuit diagram example
Outdoor unit
control PCB
Connected unit
(Locally purchased)
Example: Switch
Signal
10m*
Connector
1
2
1
2
P580PA580
Contact capacity: DC 24 V or more, 10 mA or
more.
*: Make the distance from the PCB to the
connected unit within 10 m.
Construct a circuit as shown in this figure
with using optional parts mentioned below.
Input signal: On in “Peak cut mode”
Input signal: Off in normal operation
To set the level of “Peak cut mode”, refer to
"Peak cut mode" on page 104.
On
Off
On
Off
Input signal
Peak cut mode
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
External input wire
- 98 -
12-1. External input 12. External input and output (30-45 models)
OUTDOOR UNIT
AOYG18-45KATA
OUTDOOR UNIT
AOYG18-45KATA

Table of Contents

Other manuals for Fujitsu AO G18KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G18KATA Series and is the answer not in the manual?

Fujitsu AO G18KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G18KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals