7. Additional charge calculation
7-1. Model: AOYG18KATA
Refrigerant type R32
Refrigerant amount g 900
Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge amount g 0 100
7-2. Model: AOYG22KATA
Refrigerant type R32
Refrigerant amount g 1,100
Refrigerant charge
Total pipe length m 15 or less 20 25 (Max.)
20 g/m
Additional charge amount g 0 100 200
7-3. Model: AOYG24KATA
Refrigerant type R32
Refrigerant amount g 1,250
Refrigerant charge
Total pipe length m 20 or less 25 (Max.)
20 g/m
Additional charge amount g 0 100
7-4. Models: AOYG30KATA and AOYG36KATA
Refrigerant type R32
Refrigerant amount g 1,900
There is no additional refrigerant charge in this model. (Chargeless system)
Total pipe length m 30 (Max.)
0 g/m
Additional charge amount g 0
7-5. Model: AOYG45KATA
Refrigerant type R32
Refrigerant amount g 2,400
There is no additional refrigerant charge in this model. (Chargeless system)
Total pipe length m 30 (Max.)
0 g/m
Additional charge amount g 0