¢ Medium static pressure duct type
• Compressor frequency range
Connected model name Minimum frequency Maximum frequency
AOHG45KRTA 17 rps 95 rps
AOHG54KRTA 17 rps 95 rps
• Limit of maximum speed based on outdoor temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
E zone
F zone
10°C
0°C
12°C
2°C
Outdoor
temperature drops
Outdoor
temperature rises
Unit: rps
– Models: AOHG45KRTA and AOHG54KRTA
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
ARXG22KMLA
ARXG24KMLA
A zone 95 66 51 33
B zone 95 66 51 33
C zone 80 51 41 33
D zone 56 41 35 27
E zone 56 41 35 27
F zone 56 41 35 27
1-1. Cooling operation - (04-4) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS