8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Model: AOHG36KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 3.5 A 3.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
42°C ≤ Ta < 50°C 6.0 A 5.5 A
2°C ≤ Ta < 42°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
Heating
20°C ≤ Ta 5.5 A 5.0 A
16°C ≤ Ta < 20°C 6.0 A 5.5 A
12°C ≤ Ta < 16°C 7.0 A 6.5 A
2°C ≤ Ta < 12°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
¢ Models: AOHG45KRTA and AOHG54KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 4.5 A 4.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
46°C ≤ Ta < 50°C 6.5 A 6.0 A
42°C ≤ Ta < 46°C 7.5 A 7.0 A
2°C ≤ Ta < 42°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
Heating
20°C ≤ Ta 6.5 A 6.0 A
16°C ≤ Ta < 20°C 7.0 A 6.5 A
12°C ≤ Ta < 16°C 8.0 A 7.5 A
2°C ≤ Ta < 12°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
8-3. Current release control - (04-35) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu AO G36KBTB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G36KBTB Series and is the answer not in the manual?

Fujitsu AO G36KBTB Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G36KBTB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals