- (01 - 15) -
DUCT TYPE
ARTG54LHTC
DUCT TYPE
ARTG54LHTC
HEATING CAPACITY6-2.
This table is created using the rated capacity.
MODEL
: ARTG54LH
shows rated capacity
The data is based on the following conditions. Pipe length: 7.5m, Height difference: 0m
AFR: Air Flow Rate (
m
3
/min)
TC : Total Capacity (kW)
IP : Input Power (kW)
AFR 59.2
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 12.79 4.91 12.48 5.01 12.18 5.11 11.88 5.21 11.57 5.31
-10 -11 14.22 4.91 13.88 5.01 13.54 5.11 13.20 5.21 12.86 5.31
-5 -7 15.76 4.92 15.39 5.02 15.01 5.12 14.63 5.22 14.26 5.32
0 -2 16.98 4.91 16.57 5.01 16.17 5.11 15.77 5.21 15.36 5.31
5 3 18.62 4.89 18.17 4.99 17.73 5.09 17.29 5.19 16.84 5.29
7 6 16.80 4.20 16.40 4.28 16.00 4.37 15.60 4.46 15.20 4.54
10 8 18.44 3.92 18.00 4.00 17.56 4.08 17.12 4.16 16.68 4.25
15 10 19.80 3.89 19.33 3.97 18.86 4.05 18.39 4.13 17.92 4.19
20 15 19.23 3.82 18.77 3.90 18.31 3.98 17.85 4.06 17.40 4.12
24 18 19.91 3.75 19.43 3.83 18.96 3.91 18.48 3.99 18.01 4.05