1. Specifications
Type Inverter heat pump
Model name AOU18RLXFWH AOU24RLXFWH
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—253 V
Starting current A 8.0 10.5
Fan
Airflow rate
Cooling
CFM (m
3
/h)
1,489 (2,530) 2,001 (3,400)
Heating 1,489 (2,530) 2,119 (3,600)
Type × Q'ty Propeller fan × 1
Motor output W 100
Sound pressure level *1
Cooling
dB (A)
47 54
Heating 50 55
Heat exchanger type
Dimensions
(H × W × D)
in 31-7/16 × 35-7/16 × 1-7/16
mm 798 × 900 × 36.4
Fin pitch FPI 20
Rows × Stages 2 × 38
Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum)
Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty Hermetic motor compressor × 1
Motor output W 2,100
Refrigerant
Type R410A
Charge
lb oz 4 lb 10.1 oz
g 2,100
Refrigerant oil
Type POE (RB68)
Amount
in
3
(cm
3
)
48.8 (800)
Enclosure
Material Steel sheet
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
in 32-11/16 × 35-7/16 × 13
mm 830 × 900 × 330
Gross
in 39-3/8 × 41-5/16 × 17-1/2
mm 1,000 × 1,050 × 445
Weight
Net
lb (kg)
135 (61)
Gross 152 (69)
Connection pipe
Size
Liquid
in (mm)
Ø 3/8 (Ø 9.52)
Gas Ø 5/8 (Ø 15.88)
Method Flare
Pre-charge length
ft (m)
66 (20)
Max. length 164 (50)
Max. height difference 98 (30)
Operation range
Cooling
°F (°C)
-5 to 115 (-20 to 46)
Heating -15 to 75 (-26 to 24)
Drain hose
Material LDPE
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.