“Wired remote sensor”
Using the table on the right adjust temeprature correction
by changing function setting 92.
(Room Temperature control for wired remote controller sensor)
Check Point 6 : Check Function Setting
Setting DescriptionFunction Number Setting Value
No correction 0.0°F (0.0°C)
+1°F (+0.5°C)
+2°F (+1.0°C)
+4°F (+2.0°C)
+3°F (+1.5°C)
+5°F (+2.5°C)
+6°F (+3.0°C)
+7°F (+3.5°C)
+8°F (+4.0°C)
No correction 0.0°F (0.0°C)
00
01
10
11
12
13
14
15
16
17
92
(For
cooling)
Less
Cooling
Ref.)
OK
NO
YES
Setting DescriptionFunction Number Setting Value
Indoor unit
Both
42
00
01
Setting DescriptionFunction Number Setting Value
Both
Wired remote controller
48
00
01
YES
YES
Check Point 3 : Check the remote controller display
Is the "Thermo Sensor Icon" displayed on the screen?
Check Point 3-1 : Check Function Setting
Is function 42 (Indoor room temperature sensor
switching function) set to 01?
Ref.)
Check Point 3-2 : Check the remote controller
Press and hold down the THERMO SENSOR button
to turn on the icon.
Is function 48 (Room temperature sensor switching)
set to 01?
Check Point 4 : Check the Function Setting
Check Point 4-1: Check the Function Setting
Change setting of function 48
(Room temperature sensor switching) to 01.
Ref.)
NO
NO
Check Point 4-2 : Check the effects of Function
Setting change
Did this function setting improve temperature control?
OK
Is the mounting location of the wired remote
controller affecting the temperature sensing?
(Sunlight on the remote, heat source next to the remote)
Check Point 5 : Location of the remote controller
Check Point 5-1 : Location of the remote controller
Move the remote controller.
Too cool
Too cool
Too cool