The maximum value of the indoor fan speed is set as shown in Fig 6, based on the detected
temperature by the indoor heat exchanger sensor in heating mode.
< ASU type >
01-09
5. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan will run according to a room temperature,
as shown in Fig 5.
On the other hand, if switched in [Hi] [Quiet], the indoor fan will run at a constant airflow
of [Heat] operation modes Quiet, Lo, Me, Hi, as shown in Table 2.
6. COOL AIR PREVENTION CONTROL (For Heating and Min. Heat operation)
( Fig.5 : Airflow change - over ( Heating : Auto ) )
TR-Ts > -3°F(-1.5°C)
=
-5°F(-2.5°C) > TR-Ts
-3°F(-1.5°C) > TR-Ts > -5°F(-2.5°C)
=
TR-Ts > -2°F(-1°C)
=
-4°F(-2°C) > TR-Ts
-2°F(-1°C) > TR-Ts > -4°F(-2°C)
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Lo
Me
Me+
107.6°F(42°C)
86°F
(30°C)
93.2°F
(34°C)
When Indoor heat exchanger
temperature rises
When Indoor heat exchanger
temperature drops
Hi
*Me+ or setting
FAN mode
Cool air
prevention
102.2°F
(39°C)
98.6°F
(37°C)
98.6°F
(37°C)
89.6°F
(32°C)
82.4°F
(28°C)
S-Lo
*Lo or setting
FAN mode
84.2°F
(29°C)
When Indoor heat exchanger
temperature rises
When Indoor heat exchanger
temperature drops
*Lo or setting
FAN mode
98.6°F
(37°C)
89.6°F
(32°C)
75.2°F
(24°C)
*Hi or setting
FAN mode
S-Lo
During NORMAL HEATING OPERATION
< ARU type >
*Lower speed is selected
Field setting is necessary at AR and AU type as "Cool air prevention : effective"
TR-Ts > -3°F(-1.5°C)
=
-5°F(-2.5°C) > TR-Ts
-3°F(-1.5°C) > TR-Ts > -5°F(-2.5°C)
=
TR-Ts > -2°F(-1°C)
=
-4°F(-2°C) > TR-Ts
-2°F(-1°C) > TR-Ts > -4°F(-2°C)
=
When the room
temperature rises
When the room
temperature drops
Lo
Me
Hi
< AUU/ ARU/ AGU type >
< ASU type >
( Fig.6 : Airflow change - over for cool air prevention)
*Lower speed is selected

Other manuals for Fujitsu AOU36RLXFZ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU36RLXFZ and is the answer not in the manual?

Fujitsu AOU36RLXFZ Specifications

General IconGeneral
BrandFujitsu
ModelAOU36RLXFZ
CategoryAir Conditioner
LanguageEnglish

Related product manuals