- (01 - 28) -
WALL MOUNTED TYPE
ASU9-15RLS2
WALL MOUNTED TYPE
ASU9-15RLS2
4) Auto restart
Enable or disable automatic system restart after a power outage.
(
... Factory setting)
Setting description Function number Setting value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate using the remote controller, or external input device.
5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the control by Wired remote controller
temperature sensor.
(
... Factory setting)
Setting description Function number Setting value
No
42
00
Yes 01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller
unit sensor.
6) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(
... Factory setting)
Setting description Function number Setting value
A
44
00
B 01
C 02
D 03
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
... Factory setting)
Setting description Function number Setting value
Operation/Stop mode
46
00
(Setting forbidden) 01
Forced stop mode 02

Other manuals for Fujitsu AOU9RLS2H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU9RLS2H and is the answer not in the manual?

Fujitsu AOU9RLS2H Specifications

General IconGeneral
BrandFujitsu
ModelAOU9RLS2H
CategoryAir Conditioner
LanguageEnglish

Related product manuals