SPECIFICATIONS1.
Type INVERTER HEAT PUMP
Model name AOU9RLS2H AOU12RLS2H AOU15RLS2H
Power source 208 / 230V
~
60Hz
Available voltage range 187 - 253V
~
60Hz
Starting current A 3.7 5.5 6.1
Fan
Airow
rate
Cooling
CFM
(m
3
/h)
1082 (1840) 1206 (2050)
Heating 1082 (1840)
Type × Q'ty Propeller fan × 1
Motor output W 115
Sound pressure level
Cooling
dB (A)
48 49 51
Heating 49 50 51
Heat exchanger type
Dimensions
(H × W × D)
in. 23-5/32 × 34-11/16 × 1-7/16
mm 588 × 881 × 36.4
Fin pitch FPI 20
Rows × Stages 2 × 28
Pipe type Copper
Fin Type Aluminum
Compressor
Type × Q'ty Rotary × 1
Motor output W 850 1000
Refrigerant
Type (Global Warming Potential) R410A (1975)
Charge
lbs.oz. 2lbs.10oz. 2lbs.12oz.
kg 1.20 1.25
Refrigerant oil Type FREOL α68SZ
Enclosure
Material Steel
Color
Beige
Approximate color of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
in. 24 - 1/2 × 31 - 3/32 × 11 - 11/32
mm 620 × 790 × 290
Gross
in. 28 - 1/16 × 37-7/32 × 15 - 9/16
mm 713 × 945 × 395
Weight
Net
lbs.(kg)
86 (39) 88 (40)
Gross 93 (42) 95 (43)
Connenction pipe
Size
Liquid
in. (mm)
Ø 1/4 (Ø 6.35)
Gas Ø 3/8 (Ø 9.52) Ø 1/2 (Ø 12.7)
Method Flare
Pre - charge length
ft. (m)
49 (15)
Max. length 66 (20)
Max. height difference 49 (15)
Operation range
Cooling
°F (°C)
14 to 115 (-10 to 46)
Heating -15 to 75 (-26 to 24)
Note :
Specications are based on the following conditions.
Cooling : Indoor temperature of 80°F (26.67°C) DB / 67°F (19.44°C) WB, and outdoor temperature of 95°F (35°C) DB / 75°F (23.9°C) WB.
Heating : Indoor temperature of 70°F (21.11°C) DB / 59°F (15°C) WB, and outdoor temperature of 47°F (8.33°C) DB / 43°F (6.11°C) WB.
Pipe length : 24ft.7in (7.5m), Height difference:0 m. (Outdoor unit - Indoor unit)
The protective function may work when using it outside the operation range.