3.3.1 When install nearby limited height wall
(1) Single and multiple installations
• There are no restrictions on the height of the side wall.
Provide installation spaces L1 and L2 in accordance with the table below according to the
wall height (front side, rear side) conditions.
• Provide installation spaces other than L1 and L2 in accordance with the conditions
shown in the figure below.
• Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 79 in (2 m).
Wall height condition: in (mm)
Installation requirement : in (mm)
When H1 is 59 (1,500) or less L1 20 (500)
When H1 is 59 (1,500) or more L1 20 (500) + h1 / 2
When H2 is 19 (500) or less L2 4 (100)
When H2 is 19 (500) or more L2 4 (100) + h2 / 2
Single installation
19 (500)
L1
L2
H1
h1
H2
h2
2 (30)
or more
1 (20)
or more
Unit: in (mm)
59 (1,500)
Multiple installations
19 (500)
L1
L2
H1
h1
H2
h2
2 (30)
or more
1 (20)
or more
1 (20)
or more
1 (20)
or more
Unit: in (mm)
59 (1,500)
(2) Concentrated installation
• Provide installation spaces L3, L4, and L5 in accordance with the table below according
to the wall height (front side, rear side) conditions.
• Provide installation spaces other than L3, L4, and L5 in accordance with the conditions
shown in the figure below.
• Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 79 in (2 m).
Wall height condition: in (mm) Installation requirement : in (mm)
When H3 is 59 (1,500) or less L3 20 (500)
When H3 is 59 (1,500) or more L3 20 (500) + h3 / 2
When H4 is 19 (500) or less L4 8 (200)
When H4 is 19 (500) or more L4 8 (200) + h4 / 2
When H5 is 19 (500) or less L5 8 (200)
When H5 is 19 (500) or more L5 8 (200) + h5 / 2
19 (500)
L3
L4
H3
h3
H4
h4
L5
L5
19 (500)
H5
h5
19 (500)
H5
h5
1 (20)
or more
1 (20)
or more
32 (800)
or more
32 (800)
or more
Unit: in (mm)
59 (1,500)
L5
L5
19 (500)
L3
L4
H3
h3
H4
h4
19 (500)
H5
h5
19 (500)
H5
h5
1 (20)
or more
1 (20)
or more
20 (500)
or more
40 (1,000)
or more
Unit: in (mm)
59 (1,500)
3.3.2 When install near unlimited height wall
(1) Single and multiple installations
• There are no restrictions on the height of the wall.
• The wall (without height restrictions) must not exist on the both sides (left / right) of
outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
• Provide installation spaces other than L6 in accordance with the conditions shown in the
figure below.
• Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 79 in (2 m).
When installing with the rear of the outdoor unit facing the wall side:
Wall height condition: in (mm) Installation requirement: in (mm)
When B 16 (400) L6 8 (200)
When 1 B < 16
(When 20 B < 400)
L6 8 + (16 - B) × 3
(L6 200 + (400 - B) × 3)
Single installation
8 (200)
or more
4 (100)
or more
Unit: in (mm)
Multiple installations
B
B
L6
Unit: in (mm)
8 (200)
or more
Example :
When B is made 8 in (200 mm)
L6 8 + (16 - 8) × 3 = 32 in (L6 200 + (400-200) × 3 = 800 mm)
8 (200)
or more
8 (200)
8 (200)
32 (800)
or more
Unit: in (mm)