3.3.1 When install nearby limited height wall
(1) Single and multiple installations
• There are no restrictions on the height of the side wall.
• Provide installation spaces L1 and L2 in accordance with the table below according to the
wall height (front side, rear side) conditions.
• Provide installation spaces other than L1 and L2 in accordance with the conditions
shown in the figure below.
• Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 79 in (2 m).
Wall height condition: in (mm)
Installation requirement : in (mm)
When H1 is 59 (1,500) or less L1 ≥ 20 (500)
When H1 is 59 (1,500) or more L1 ≥ 20 (500) + h1 / 2
When H2 is 19 (500) or less L2 ≥ 4 (100)
When H2 is 19 (500) or more L2 ≥ 4 (100) + h2 / 2
Single installation
19 (500)
L1
L2
H1
h1
H2
h2
2 (30)
or more
1 (20)
or more
Unit: in (mm)
59 (1,500)
Multiple installations
19 (500)
L1
L2
H1
h1
H2
h2
2 (30)
or more
1 (20)
or more
1 (20)
or more
1 (20)
or more
Unit: in (mm)
59 (1,500)
(2) Concentrated installation
• Provide installation spaces L3, L4, and L5 in accordance with the table below according
to the wall height (front side, rear side) conditions.
• Provide installation spaces other than L3, L4, and L5 in accordance with the conditions
shown in the figure below.
• Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 79 in (2 m).
Wall height condition: in (mm) Installation requirement : in (mm)
When H3 is 59 (1,500) or less L3 ≥ 20 (500)
When H3 is 59 (1,500) or more L3 ≥ 20 (500) + h3 / 2
When H4 is 19 (500) or less L4 ≥ 8 (200)
When H4 is 19 (500) or more L4 ≥ 8 (200) + h4 / 2
When H5 is 19 (500) or less L5 ≥ 8 (200)
When H5 is 19 (500) or more L5 ≥ 8 (200) + h5 / 2
19 (500)
L3
L4
H3
h3
H4
h4
L5
L5
19 (500)
H5
h5
19 (500)
H5
h5
1 (20)
or more
1 (20)
or more
32 (800)
or more
32 (800)
or more
Unit: in (mm)
59 (1,500)
L5
L5
19 (500)
L3
L4
H3
h3
H4
h4
19 (500)
H5
h5
19 (500)
H5
h5
1 (20)
or more
1 (20)
or more
20 (500)
or more
40 (1,000)
or more
Unit: in (mm)
59 (1,500)
3.3.2 When install near unlimited height wall
(1) Single and multiple installations
• There are no restrictions on the height of the wall.
• The wall (without height restrictions) must not exist on the both sides (left / right) of
outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
• Provide installation spaces other than L6 in accordance with the conditions shown in the
figure below.
• Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 79 in (2 m).
When installing with the rear of the outdoor unit facing the wall side:
Wall height condition: in (mm) Installation requirement: in (mm)
When B ≥ 16 (400) L6 ≥ 8 (200)
When 1 ≤ B < 16
(When 20 ≤ B < 400)
L6 ≥ 8 + (16 - B) × 3
(L6 ≥ 200 + (400 - B) × 3)
Single installation
8 (200)
or more
4 (100)
or more
Unit: in (mm)
Multiple installations
B
B
L6
Unit: in (mm)
8 (200)
or more
Example :
When B is made 8 in (200 mm)
L6 ≥ 8 + (16 - 8) × 3 = 32 in (L6 ≥ 200 + (400-200) × 3 = 800 mm)
8 (200)
or more
8 (200)
8 (200)
32 (800)
or more
Unit: in (mm)