Control output function
Operation/Stop status
Rotary SW on External
input and output PCB
External output
Output
signal
Command
1
B
C
D
External input and output PCB CN310
Off → On Operation
On → Off Stop
The output is low when the unit is stopped.
Operation
Stop
On
Off
CN310
Indoor unit
Error status
Rotary SW on External
input and output PCB
External output
Output
signal
Command
1
C
External input and output PCB
CN311
Off → On Error
On → Off Normal
D CN312
Off → On Error
On → Off Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
On
Off
CN311―312
Indoor unit
Indoor unit fan operation status
Rotary SW on External
input and output PCB
External output
Output
signal
Command
1
External input and output PCB
CN312
Off → On Fan run
On → Off Fan stop
2
B
D
CN311
Off → On Fan run
On → Off Fan stop
Output signal Condition
On
The indoor unit fan is operating.
Low → High
Off The fan is stopped or during cold air prevention.
High → Low During thermostat off when in dry mode operation.
Fan run
Fan stop
On
Off
CN311―312
Indoor unit
- 29 -
9-4. Details of function 9. External input and output
WALL MOUNTED
ASUG09-15LZAS
WALL MOUNTED
ASUG09-15LZAS

Table of Contents

Other manuals for Fujitsu AOUG09LZAS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOUG09LZAS1 and is the answer not in the manual?

Fujitsu AOUG09LZAS1 Specifications

General IconGeneral
BrandFujitsu
ModelAOUG09LZAS1
CategoryAir Conditioner
LanguageEnglish

Related product manuals