1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
If the room temperature is 11°F (6.0°C) lower than a set temperature, the operation rotation num-
ber of compressor will attain to maximum performance.
If the room temperature is 2°F (1.0°C) higher than a set temperature, the compressor will be
stopped.
When the room temperature is within the range of +2°F (1.0°C) to -11°F (6.0°C) of the setting tem-
perature, the rotation number of compressor is controlled within the range shown below.
Rotation number range of compressor
Unit: rps
Model name Minimum rotation number Maximum rotation number
ASUH09LMAS
ASUH12LMAS
12 110
Limit of maximum speed based on outdoor temperature
In heating operation, maximum rotation number is defined by outdoor temperature and fan mode.
A zone
B zone
C zone
Outdoor
temperature rises
Outdoor
temperature drops
57.2°F
(14°C)
66.2°F
(19°C)
53.6°F
(12°C)
62.6°F
(17°C)
Unit: rps
Model name
Outdoor
temperature zone
Indoor unit fan mode
HIGH MED LOW QUIET
ASUH09LMAS
ASUH12LMAS
A zone 110 89 77 67
B zone 110 89 77 67
C zone 110 89 77 36
1-2. Heating operation - (04-2) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS