1-5. Limitation of compressor rotation number by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
E zone
D zone
C zone
B zone
A zone
14.0°F
(-10°C)
32.0°F
(0°C)
50.0°F
(10°C)
66.2°F
(19°C)
100.4°F
(38°C)
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
rotation number
AOUH09LMAH1
AOUH12LMBH1
A zone 35
B zone 35
C zone 35
D zone 15
E zone 15
F zone 36
Heating mode
F zone
E zone
D zone
C zone
B zone
A zone
66.2°F
(19°C)
32.0°F
(0°C)
5.0°F
(-15°C)
-13.0°F
(-25°C)
41.0°F
(5°C)
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
rotation number
AOUH09LMAH1
AOUH12LMBH1
A zone 54
B zone 37
C zone 36
D zone 15
E zone 15
F zone 1
1-5. Limitation of compressor rotation number by outdoor temperature - (04-4) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS