EasyManua.ls Logo

Fujitsu AOUH24LMAS1 - Page 35

Fujitsu AOUH24LMAS1
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
External heater output
Function setting /
Rotary SW on
External input
and output PCB
External output
Output
signal
Command
60-11 / D Output of indoor unit CN47
Off → On Heater on
On → Off Heater off
60-00 / 2
External input and
output PCB
CN312
Off → On Heater on
60-09 / B
60-10 / C
On → Off Heater off
Set point attainment status
NOTE: This function is valid only when function setting 96 is set to “Enable” (01).
When the room temperature does not reach the set point at a room due to the lower cooling per-
formance caused by external factor such as the outdoor temperature change, signal is output to
tell the attainment status of set point.
Function setting /
Rotary SW on
External input
and output PCB
External output
Output
signal
Command
60-12 / D Output of indoor unit CN47
On → Off Normal
Off → On
Set point
attainment
Output signal Condition
Off Reached the set point. (Tr ≤ Tsα +1°F [0.5°C])
On
Unreached the set point. (Tr > Tsα +5°F [2.5°C])
However, even if the set point unreached, the signal will not be output for 7 minutes
after power is turned on.
Tr > Tsα + 5°F (2.5°C)
Output: On
Output: Off
Tr ≤ Tsα + 1°F (0.5°C)
When starting operation*
*: When starting operation or resetting, judges the zone to descending direction.
- 31 -
8-4. Details of function
8. External input and output
WALL MOUNTED
ASUH18-24LMAS
WALL MOUNTED
ASUH18-24LMAS

Table of Contents

Other manuals for Fujitsu AOUH24LMAS1

Related product manuals