7. Additional charge calculation
7-1. Model: AOUH18LMAS1
Refrigerant type R410A
Factory charge amount
lb oz 3 lb 15 oz
g 1,800
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 99 131 165 (Max.)
0.43 oz/ft
(40 g/m)
m 15 or less 20 30 40 50 (Max.)
Additional
charge
lb oz 0 7 oz 1 lb 5 oz 2 lb 3 oz 3 lb 1 oz
g 0 200 600 1,000 1,400
7-2. Model: AOUH24LMAS1
Refrigerant type R410A
Factory charge amount
lb oz 4 lb 10 oz
g 2,100
¢ Refrigerant charge
Total pipe length
ft 65 or less 99 131 165 (Max.)
0.43 oz/ft
(40 g/m)
m 20 or less 30 40 50 (Max.)
Additional charge
lb oz 0 14 oz 1 lb 12 oz 2 lb 10 oz
g 0 400 800 1,200
- 77 -
7-1. Model: AOUH18LMAS1
7. Additional charge calculation
OUTDOOR UNIT
AOUH18-24LMAS1
OUTDOOR UNIT
AOUH18-24LMAS1