Available Sensor ID
Sensor ID Item Unit Remarks
00 057 Limit switch 3 (For left filter) On/Off 08: On/Off 0: Off, 1: On
00 070 Current sensor 09: A
00 080 Indoor unit total energized hours 11: h
00 081 Total filtering hours 11: h
00 082 Indoor unit fan total operation hours 11: h
00 083 Indoor unit fan 2 total operation hours 11: h
00 084 Indoor unit fan 3 total operation hours 11: h
00 090 Temperature sensor 12: %
00 095
Presence or absence detected by
human sensor
00: —
0: Absence, 1: Presence
—: Human sensor error or No human
sensor
00 140 Operation or Stop (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 141 Emergency stop (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 142 Forced stop (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 143 Operation or Stop 2 (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 144
External thermostat off (External
input)
00: — 0: Off, 1: On
00 145 Cooling operation on (External input) 00: — 0: Off, 1: On
00 146
Cooling operation off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 155
Operation or Stop On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 156 Error On/Off (External output) 00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 157
Indoor unit fan interlocking On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 158
Cooling thermostat On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 159
Requested cooling strength On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
7-14. Unit status monitoring and the detected value indication - (04-28) - 7. Various control