Available Sensor ID
Sensor ID Item Unit Remarks
00 160
External heater On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 161
Heating operation status (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 162
External output command by remote
controller (External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 163
Set-point temp. not reached in server
room function On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
01: Outdoor unit
01 000 Outdoor temp. 01: °F or °C
01 001 Discharge temp. 01: °F or °C
01 002 Suction temp. 01: °F or °C
01 003 Heat exchanger middle temp. 01: °F or °C
01 004 Heat exchanger outlet temp. 01: °F or °C
01 005
Liquid pipe temp. (Before expansion
valve)
01: °F or °C
01 006
Liquid pipe temp. 2 (After expansion
valve)
01: °F or °C
01 007 Compressor temp. 01: °F or °C
01 008 Heat sink temp. 01: °F or °C
01 009
Liquid pipe temp. 3 (Sub cool heat
exchanger inlet)
01: °F or °C
01 010
Liquid pipe temp. 4 (Sub cool heat
exchanger outlet)
01: °F or °C
01 011
2-way valve temp. (For multi-split
type)
01: °F or °C
01 012
3-way valve temp. (For multi-split
type)
01: °F or °C
01 040 Discharge pressure 02: MPa
01 041 Suction pressure 02: MPa
01 042 Gas pipe pressure for outdoor unit 02: MPa
01 050 Fan 1 rotation number 03: rpm
01 051 Fan 2 rotation number 03: rpm
01 055 Compressor rotation number 04: rps
01 060
Expansion valve (Upstream during
heating)
05: pls
01 061
Expansion valve 2 (Downstream
during heating)
05: pls
01 062
Expansion valve 3 (For sub cool heat
exchanger)
05: pls
01 063 Expansion valve 4 (For injection) 05: pls
01 064
Expansion valve 5 (For multi-split
type)
05: pls
01 075 Solenoid valve (For injection) 06: Open/Close 0: Close, 1: Open
01 080 4-way valve output status
07: Cooling/
Heating
0: Cooling, 1: Heating
01 085 Pressure switch (High pressure) 08: On/Off 0: Off (Close), 1: On (Open)
01 086 Pressure switch (Low pressure) 08: On/Off 0: Off (Close), 1: On (Open)
01 088 Crankcase heater output On/Off 08: On/Off 0: Off, 1: On
7-14. Unit status monitoring and the detected value indication - (04-29) - 7. Various control