15. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 12.
If the remote control is lost or battery power dissipated, this function will work without the remote
control.
OPERATION MODE Auto changeover
FAN CONT. MODE Auto
TIMER MODE Continuous
SETTING TEMP. 24 C
SETTING LOUVER Standard
SWING OFF
When the outdoor heat exchanger temperature is lower than temperature and the heating operation has
been stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to temperature or greater, preheating
is ended.
AS*9LSACW
AS*12LSACW
AS*9LSBCW
AS*12LSBCW
AS*14LSBCW
AS*18LSBCW
AS*9LSACW
900rpm 36Hz
AS*12LSACW
900rpm 36Hz
AS*9LSBCW
900rpm 36Hz
AS*12LSBCW
900rpm 36Hz
AS*14LSBCW
900rpm 24Hz
AS*18LSBCW
900rpm 24Hz
(Table 12)
(No timer setting available)
16. COMPRESSOR PREHEATING
(Table 13 : Preheating Operation / Release Temperature)
Temperature
Temperature
5 C
5 C
5 C
5 C
5 C
5 C
7 C
7 C
7 C
7 C
7 C
7 C
17. COIL DRY OPERATION CONTROL
The coil-dry operation functions by pressing Coil Dry operation button on the remote controller.
The coil-dry operation is consisted of 3 cycles of [Fan operation 3 minutes / Heating operation
2 minutes], and Fan operates for 3 minutes at last before ending the air conditioner operation.
(It takes 18 minutes to complete the coil-dry operation.)
Following table indicates the indoor unit setting on the coil-dry operation.
(Table 14 : Coil-dry Operating Functions)
Indoor Fan Speed
Compressor
Frequency
Louver
Position
Main Unit
Indocation
Coil-dry indication : ON
Other indication : OFF
05-13