02 - 11
)
-
OUTDOOR UNIT
AO
G09-14LT
OUTDOOR UNIT
AO
G09-14LT
ADDITIONAL CHARGE CALCULATION6.
MODEL
:AO
G09LT
Refrigerant charge
MODEL
:AO
G12LT
Refrigerant charge
MODEL
:AO
G14LT
Refrigerant charge
Refrigerant type R410A
Refrigerant amount g 1050
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1200
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1250
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100