1-5. Limitation of compressor rotation number by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
rotation number
AOYG07KMCC
AOYG09KMCC
AOYG12KMCC
A zone 42
B zone 42
C zone 33
D zone 28
E zone 16
F zone 21
AOYG14KMCC
A zone 36
B zone 36
C zone 28
D zone 26
E zone 1
F zone 36
1-5. Limitation of compressor rotation number by outdoor temperature - (04-6) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS