Loading...
6-3. Model: AOYG24KBTB
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
25 0.893 0.877
20 0.917 0.900 0.885
10 0.966 0.947 0.932 0.914 0.899
7.5 0.979 0.970 0.951 0.936 0.918 0.903
5 0.992 0.983 0.974 0.955 0.939 0.922 0.906
0 1.000 0.991 0.981 0.963 0.946 0.930 0.914
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.991 0.981 0.963 0.946 0.930 0.914
-7.5 0.991 0.981 0.963 0.946 0.930 0.914
-10 0.981 0.963 0.946 0.930 0.914
-20 0.946 0.930 0.914
-25 0.930 0.914
HEATING
Pipe length (m)
5 7.5 10 15 20 25 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
25 0.871 0.855
20 0.887 0.871 0.855
10 0.952 0.903 0.887 0.871 0.855
7.5 0.976 0.952 0.903 0.887 0.871 0.855
5 1.000 0.976 0.952 0.903 0.887 0.871 0.855
0 1.000 0.976 0.952 0.903 0.887 0.871 0.855
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.971 0.947 0.899 0.883 0.866 0.850
-7.5 0.969 0.945 0.897 0.881 0.865 0.849
-10 0.942 0.894 0.879 0.863 0.847
-20 0.869 0.854 0.838
-25 0.850 0.834
- 84 -
6-3. Model: AOYG24KBTB 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG18-45KBTB
OUTDOOR UNIT
AOYG18-45KBTB

Table of Contents