EasyManua.ls Logo

Fujitsu AOYG18KMTA - Page 37

Fujitsu AOYG18KMTA
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTES:
The air conditioner custom code is set to
prior to shipment.
If you do not know the air conditioner custom code setting, try each of the custom codes (
) until you find the code that operates the air conditioner.
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 11 Filter sign
2) 30/31 Room temperature control for indoor unit sensor
3) 35/36 Room temperature control for wired remote controller sensor
4) 40 Auto restart
5) 42 Room temperature sensor switching
6) 44 Remote controller custom code
7) 46 External input control
8) 48 Room temperature sensor switching (Aux.)
9) 49 Indoor unit fan control for energy saving for cooling
10) 60 Switching functions for external output terminal
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard (400 hours)
01 Long interval (1,000 hours)
02 Short interval (200 hours)
03 No indication
- 33 -
11-1. Function settings by using remote controller 11. Function settings
WALL MOUNTED
ASYG18-24KMTE
WALL MOUNTED
ASYG18-24KMTE

Related product manuals