EasyManua.ls Logo

Fujitsu AOYG18KMTA - Outdoor Unit Capacity Compensation

Fujitsu AOYG18KMTA
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOYG18KMTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20 0.917 0.900
10 0.966 0.947 0.932 0.914
7.5 0.979 0.970 0.951 0.936 0.918
5 0.992 0.983 0.974 0.955 0.939 0.922
0 1.000 0.991 0.981 0.963 0.946 0.930
Indoor unit is lower than
outdoor unit *
2
-5 1.000 0.991 0.981 0.963 0.946 0.930
-7.5 0.991 0.981 0.963 0.946 0.930
-10 0.981 0.963 0.946 0.930
-20 0.946 0.930
HEATING
Pipe length (m)
5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20 0.887 0.871
10 0.952 0.903 0.887 0.871
7.5 0.976 0.952 0.903 0.887 0.871
5 1.000 0.976 0.952 0.903 0.887 0.871
0 1.000 0.976 0.952 0.903 0.887 0.871
Indoor unit is lower than
outdoor unit *
2
-5 0.995 0.971 0.947 0.899 0.883 0.866
-7.5 0.969 0.945 0.897 0.881 0.865
-10 0.942 0.894 0.879 0.863
-20 0.869 0.854
- 53 -
6-1. Model: AOYG18KMTA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG18-24KMTA
OUTDOOR UNIT
AOYG18-24KMTA

Related product manuals