En-2
CAUTION
2-2Work
Priortobeginningworkonsystemscontainingammablerefrigerants,safetychecks•
are necessary to ensure that the risk of ignition is minimized. For repair to the refrig-
erating system, the precautions in 2-2 to 2-8 shall be complied with prior to conduct-
ing work on the system.
Workshallbeundertakenunderacontrolledproceduresoastominimizetheriskof•
aammablegasorvapourbeingpresentwhiletheworkisbeingperformed.
Allmaintenancestaffandothersworkinginthelocalareashallbeinstructedonthe•
nature of work being carried out.
Workinconnedspacesshallbeavoided.•
The area around the workspace shall be sectioned off.•
Ensurethattheconditionswithintheareahavebeenmadesafebycontrolofam-•
mable material.
2-3 Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during •
work,toensurethetechnicianisawareofpotentiallyammableatmospheres.
Ensurethattheleakdetectionequipmentbeingusedissuitableforusewitham-•
mable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.
2-4Presenceofreextinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated •
parts,appropriatereextinguishingequipmentshallbeavailableathand.
Have a dry powder or CO•
2
reextinguisheradjacenttothechargingarea.
2-5Noignitionsources
Nopersoncarryingoutworkinrelationtoarefrigerationsystemwhichinvolves•
exposinganypipeworkthatcontainsorhascontainedammablerefrigerantshall
useanysourcesofignitioninsuchamannerthatitmayleadtotheriskofreor
explosion.
Allpossibleignitionsources,includingcigarettesmoking,shouldbekeptsufciently•
far away from the site of installation, repairing, removing and disposal, during which
ammablerefrigerantcanpossiblybereleasedtothesurroundingspace.
Priortoworktakingplace,theareaaroundtheequipmentistobesurveyedtomake•
surethattherearenoammablehazardsorignitionrisks.“NoSmoking”signsshall
be displayed.
2-6Ventilatedarea
Ensure that the area is in the open or that it is adequately ventilated before breaking •
into the system or conducting any hot work.
Adegreeofventilationshallcontinueduringtheperiodthattheworkiscarriedout.•
Theventilationshouldsafelydisperseanyreleasedrefrigerantandpreferablyexpel•
itexternallyintotheatmosphere.
2-7 Checks to the refrigeration equipment
Whereelectricalcomponentsarebeingchanged,theyshallbetforthepurpose•
andtothecorrectspecication.
Atalltimesthemanufacturer’smaintenanceandserviceguidelinesshallbefollowed.•
If in doubt consult the manufacturer’s technical department for assistance.•
Thefollowingchecksshallbeappliedtoinstallationsusingammablerefrigerants.•
- The charge size is in accordance with the room size within which the refrigerant
containing parts are installed.
- The ventilation machinery and outlets are operating adequately and are not
obstructed.
- If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant.
- Marking to the equipment continues to be visible and legible. Markings and signs
that are illegible shall be corrected.
- Refrigeration pipe or components are installed in a position where they are unlikely
tobeexposedtoanysubstancewhichmaycorroderefrigerantcontainingcompo-
nents, unless the components are constructed of materials which are inherently
resistant to being corroded or are suitably protected against being so corroded.
2-8 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks •
and component inspection procedures.
Ifafaultexiststhatcouldcompromisesafety,thennoelectricalsupplyshallbecon-•
nected to the circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to continue operation, •
an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised.•
Initial safety checks shall include.•
-Thatcapacitorsaredischarged:thisshallbedoneinasafemannertoavoidpos-
sibility of sparking.
-Thattherenoliveelectricalcomponentsandwiringareexposedwhilecharging,
recovering or purging the system.
- That there is continuity of earth bonding.
CAUTION
3-Repairs to sealed components
Duringrepairstosealedcomponents,allelectricalsuppliesshallbedisconnected•
from the equipment being worked upon prior to any removal of sealed covers, etc.
If it is absolutely necessary to have an electrical supply to equipment during servic-•
ing, then a permanently operating form of leak detection shall be located at the most
critical point to warn of a potentially hazardous situation.
Particularattentionshallbepaidtothefollowingtoensurethatbyworkingonelectri-•
cal components, the casing is not altered in such a way that the level of protection is
affected.
Thisshallincludedamagetocables,excessivenumberofconnections,terminalsnot•
madetooriginalspecication,damagetoseals,incorrectttingofglands,etc.
Ensure that apparatus is mounted securely.•
Ensure that seals or sealing materials have not degraded such that they no longer •
servethepurposeofpreventingtheingressofammableatmospheres.
Replacementpartsshallbeinaccordancewiththemanufacturer’sspecications.•
NOTE:Theuseofsiliconsealantmayinhibittheeffectivenessofsometypesofleak
detection equipment.
Intrinsically safe components do not have to be isolated prior to working on
them.
4-Repair to intrinsically safe components
Donotapplyanypermanentinductiveorcapacitanceloadstothecircuitwithout•
ensuringthatthiswillnotexceedthepermissiblevoltageandcurrentpermittedfor
the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in •
thepresenceofaammableatmosphere.
The test apparatus shall be at the correct rating.•
Replacecomponentsonlywithpartsspeciedbythemanufacturer.•
Other parts may result in the ignition of refrigerant in the atmosphere from a leak.•
5-Cabling
Checkthatcablingwillnotbesubjecttowear,corrosion,excessivepressure,vibra-•
tion, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual vibration from •
sources such as compressors or fans.
6-Detectionofammablerefrigerants
Undernocircumstancesshallpotentialsourcesofignitionbeusedinthesearching•
for or detection of refrigerant leaks.
Ahalidetorch(oranyotherdetectorusinganakedame)shallnotbeused.•
7-Leak detection methods
Electronicleakdetectorsshallbeusedtodetectammablerefrigerants,butthe•
sensitivitymaynotbeadequate,ormayneedre-calibration.(Detectionequipment
shallbecalibratedinarefrigerant-freearea.)
Ensure that the detector is not a potential source of ignition and is suitable for the •
refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant •
and shall be calibrated to the refrigerant employed and the appropriate percentage of
gas(25%maximum)isconrmed.
Leakdetectionuidsaresuitableforusewithmostrefrigerantsbuttheuseof•
detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
Ifaleakissuspected,allnakedamesshallberemoved/extinguished.•
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall •
berecoveredfromthesystem,orisolated(bymeansofshutoffvalves)inapartof
the system remote from the leak.
Oxygenfreenitrogen(OFN)shallthenbepurgedthroughthesystembothbefore
and during the brazing process.
8-Removal and evacuation
Whenbreakingintotherefrigerantcircuittomakerepairs–orforanyother •
purpose–conventionalproceduresshallbeused.
However,itisimportantthatbestpracticeisfollowedsinceammabilityisaconsid-
eration.
Thefollowingprocedureshallbeadheredto:
remove refrigerant•
purge the circuit with inert gas•
evacuate•
purge again with inert gas•
open the circuit by cutting or brazing•
The refrigerant charge shall be recovered into the correct recovery cylinders. •
Thesystemshallbe“ushed”withOFNtorendertheunitsafe.•
This process may need to be repeated several times. •
Compressedairoroxygenshallnotbeusedforthistask.•
FlushingshallbeachievedbybreakingthevacuuminthesystemwithOFNand•
continuingtolluntiltheworkingpressureisachieved,thenventingtoatmosphere,
andnallypullingdowntoavacuum.
This process shall be repeated until no refrigerant is within the system. •
WhenthenalOFNchargeisused,thesystemshallbeventeddowntoatmospheric•
pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe work are to take •
place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and •
there is ventilation available.