02-07
Trouble shooting 5
OUTDOOR UNIT Error Method:
Indicate or Display:
Indoor unit capacity error
Refer to error code table.
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Outdoor Unit Main PCB
When the total capacity of indoor units does not match
outdoor capacity while 3 minutes after power-on.
1. The selection of indoor units is incorrect 2. Main PCB failure
Check Point 1 : Check the total capacity of indoor unit
Check the total capacity of the connected indoor units.
>> If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB.