6-2. Outdoor unit
¢ Discharge temperature thermistor
Temperature (°C) Resistance (kΩ) Voltage (V)
-30.0 1,013.11 0.06
-25.0 729.09 0.09
-20.0 531.56 0.12
-15.0 392.31 0.16
-10.0 292.91 0.21
-5.0 221.09 0.28
0.0 168.60 0.36
5.0 129.84 0.46
10.0 100.91 0.57
15.0 79.12 0.71
20.0 62.55 0.86
25.0 49.84 1.03
30.0 40.01 1.23
35.0 32.35 1.43
40.0 26.34 1.65
45.0 21.58 1.88
50.0 17.79 2.11
55.0 14.75 2.34
60.0 12.30 2.57
65.0 10.32 2.79
70.0 8.70 3.00
75.0 7.36 3.19
80.0 6.27 3.37
85.0 5.36 3.54
90.0 4.60 3.69
95.0 3.96 3.83
100.0 3.43 3.96
105.0 2.98 4.07
110.0 2.60 4.17
115.0 2.27 4.26
120.0 2.00 4.33
6-2. Outdoor unit - (03-95) - 6. Thermistor resistance values