Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
Indicate or Display:
Check Point 2: Replace Main PCB
Outdoor unit Main PCB
Compressor
Trouble shooting 29
OUTDOOR UNIT Error Method:
Trip detection
If Check Point 1 do not improve the symptom, change Main PCB.
02-30
OKOK
Check Point 3: Replace Compressor
If Check Point 2 do not improve the symptom, change Compressor.
1. Outdoor unit fan operation defective, foreign matter on hear exchanger,
excessive rise of ambient temperature
2.Main PCB
3.Inverter compressor failure (lock, winding short)
"Protection stop by overcurrent generation after inverter compressor start
processing completed'' generated consecutively 10 times.
*The number of generations is reset if the start-up of
the compressor succeeds.
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
Error code : 94
Outdoor unit : No indication

Table of Contents

Other manuals for Fujitsu ARXG07KLLAP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG07KLLAP and is the answer not in the manual?

Fujitsu ARXG07KLLAP Specifications

General IconGeneral
Cooling Capacity2.0 kW
Heating Capacity2.5 kW
RefrigerantR32
Power Supply220-240 V, 50 Hz
Noise Level (Indoor)21 dB(A)
TypeSplit System Air Conditioner

Related product manuals