Combination of external input and output
By combining the function setting of the indoor unit, you can select various combinations of func-
tions.
Combination examples of external input and output are as follows:
Mode Function setting
External input External output
Terminal CN47
0 60—00 Operation/Stop
1—8 60—01 to 60—08 (Setting prohibited)
9 60—09 Operation/Stop Error status
10 60—10 Operation/Stop Indoor unit fan operation status
11 60—11 Operation/Stop External heater output
NOTE: Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (R.C. disabled)
Input signal type
Indoor unit
Input signal type is only "Edge".
Edge
- 152 -
11-1. Compact cassette type, Mini duct type, Slim duct type, and Medium static pressure
duct type
11. External input and output
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE