2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
Wired remote
controller
Error code E: 12
Detective actuator
Indoor unit Main PCB When the indoor unit cannot receive the signal from
wired remote controller more than following time during
normal operation.
3-wire type: 1 minute
2-wire type: 2.5 minutes
Wired remote control
Forecast of cause
Terminal connection abnormal
Wired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point : Check Wired remote controller
and main PCB
If it is DC 12 V, remote controller is failure.
(Main PCB is normal)
Replace remote control
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
Replace main PCB
Check voltage at CN14 of main PCB
(terminal 1—3, terminal 1—2). (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
End
2-3. E: 12. Wired remote controller communication error (Indoor unit) - (03-8) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ARXG45KHTA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG45KHTA and is the answer not in the manual?

Fujitsu ARXG45KHTA Specifications

General IconGeneral
BrandFujitsu
ModelARXG45KHTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals