3-3. No operation (Power is on)
Forecast of cause
Setting/ Connection failure
External cause
Electrical components defective
Check point 1. Check indoor and outdoor installation condition
-> If there is some abnormal condition, correct it by referring to the installation manual and “DESIGN
& TECHNICAL MANUAL”.
Turn off the power and check correct followings.
Is there loose or removed communication line of indoor unit and outdoor unit?
Check point 2. Check external cause at indoor and outdoor (Voltage drop or Noise)
Instant drop: Check if there is a large load electric apparatus in the same circuit.
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point . Replace main PCB
If check point 1 to do not improve the symptom, change main PCB.
End
3-3. No operation (Power is on) - (03-47) - 3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ARXG45KHTA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG45KHTA and is the answer not in the manual?

Fujitsu ARXG45KHTA Specifications

General IconGeneral
BrandFujitsu
ModelARXG45KHTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals