EasyManua.ls Logo

Fujitsu ARXG45KMLA - Service Parts Troubleshooting

Fujitsu ARXG45KMLA
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-3. Model: AOYG36KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.902
20 0.938 0.917
10 0.973 0.953 0.933
7.5 0.988 0.977 0.957 0.936
5 0.992 0.992 0.981 0.961 0.940
0 1.000 1.000 0.989 0.968 0.947
Indoor unit is lower
than outdoor unit *2
-5 1.000 1.000 0.989 0.968 0.947
-7.5 1.000 0.989 0.968 0.947
-10 0.989 0.968 0.947
-20 0.968 0.947
-30 0.947
HEATING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.978
20 0.988 0.978
10 0.998 0.988 0.978
7.5 1.000 0.998 0.988 0.978
5 1.000 1.000 0.998 0.988 0.978
0 1.000 1.000 0.998 0.988 0.978
Indoor unit is lower
than outdoor unit *2
-5 0.995 0.995 0.993 0.983 0.973
-7.5 0.993 0.991 0.981 0.971
-10 0.988 0.978 0.968
-20 0.968 0.958
-30 0.949
- 87 -
6-3. Model: AOYG36KATA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG24-45KATA
OUTDOOR UNIT
AOYG24-45KATA

Table of Contents

Other manuals for Fujitsu ARXG45KMLA

Related product manuals