5-2. Outdoor unit
¢ Heatsink thermistor
Temperature (°C) Resistance (kΩ) Voltage (V)
-30.0 94.26 0.08
-25.0 67.95 0.11
-20.0 49.62 0.15
-15.0 36.68 0.20
-10.0 27.42 0.26
-5.0 20.73 0.34
0.0 15.83 0.43
5.0 12.21 0.55
10.0 9.50 0.68
15.0 7.46 0.84
20.0 5.90 1.01
25.0 4.71 1.21
30.0 3.78 1.42
35.0 3.06 1.64
40.0 2.50 1.88
45.0 2.05 2.11
50.0 1.69 2.35
55.0 1.40 2.58
60.0 1.17 2.81
65.0 0.98 3.02
70.0 0.83 3.22
75.0 0.70 3.41
80.0 0.60 3.58
85.0 0.51 3.73
90.0 0.44 3.87
95.0 0.38 3.99
100.0 0.33 4.10
5-2. Outdoor unit - (03-59) - 5. Thermistor resistance values