2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
→ired remote
controller
Error code E: 12
Detective actuator
Indoor unit Main PCB →hen the indoor unit cannot receive the signal from
wired remote controller more than following time during
normal operation.
• 3-wire type: 1 minute
• 2-wire type: 2.5 minutes
→ired remote control
Forecast of cause
Terminal connection abnormal
→ired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
• Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point 2 : Check →ired remote controller
and main PCB
• If it is DC 13 V, remote controller is failure.
(Main PCB is normal)
– Replace remote control
• If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
– Replace main PCB
Check voltage at CN300 of main PCB
(terminal 1—3, terminal 1—2). (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
End
2-3. E: 12. →ired remote controller communication error (Indoor unit) - (03-8) - 2. Troubleshooting with error code
TROUBLESHOOTING