2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
→ired remote
controller
Error code E: 12
Detective actuator
Indoor unit Main PCB →hen the indoor unit cannot receive the signal from
wired remote controller more than following time during
normal operation.
3-wire type: 1 minute
2-wire type: 2.5 minutes
→ired remote control
Forecast of cause
Terminal connection abnormal
→ired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point 2 : Check →ired remote controller
and main PCB
If it is DC 13 V, remote controller is failure.
(Main PCB is normal)
Replace remote control
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
Replace main PCB
Check voltage at CN300 of main PCB
(terminal 1—3, terminal 1—2). (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
End
2-3. E: 12. →ired remote controller communication error (Indoor unit) - (03-8) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ARXG45KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG45KMLA and is the answer not in the manual?

Fujitsu ARXG45KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG45KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals