Page #68 background image
2-19. E: 65. Trip terminal L error (Outdoor unit)
Indicator
→ired remote
controller
Error code E: 65
Detective actuator Outdoor unit Main PCB
→hen the signal from FO terminal of IPM is “L” (0 V)
during the compressor stopping.
Forecast of cause Main PCB failure
Check point 1. Check main PCB
Replace the outdoor unit main PCB.
End